What can cause flooding of the connections in a steam heater control system?

Higher speeds of the condensate can lead flooding of the connections by accumulation of condensate. It is recommended that the velocity of the condensate is below approximately 0.5 m/s so the condensate outlet will be self-venting.
See the user manual Compabloc IOM Manual.pdf for more details.